Modular UPS-High Frequency Online Uninterrupted Power Supply MPS9335C Ⅱ 50-720KVA
Contact Person : Ella
Phone Number : 0755-81495850
WhatsApp : +8613682556888
Minimum Order Quantity : | USD10000 | Packaging Details : | Standard Exported Cartons and Pallets |
---|---|---|---|
Delivery Time : | Within 15-30days after receiving your 30% TT deposit | Payment Terms : | 30% TT in advance, the balance before shipping |
Supply Ability : | 10000PCS/Month for Inverter and line Interactive UPS; Advance 3000PCS/Month for Online UPS |
Place of Origin: | China | Brand Name: | SOROTEC |
---|---|---|---|
Certification: | CE,ROHS,ISO9000 |
Detail Information |
|||
High Light: | ups battery cabinet,remote control ups |
---|
Product Description
60Hz RS485 Modular UPS for data processing centers LCD display 5KVA - 210KVA
Key Features
Applications
Data processing centers, computer systems, servers, communication systems, financial systems, servers, communication systems, financial systems, traffic systems, medical systems, and many other fields.
Technical Specifications of Modular UPS, MPS9330 5KVA-210KVA
Model |
MPS9330 5KVA-210KVA |
Single module capacity |
5KVA 10KVA 15KVA |
System capacity |
5-210KVA |
Rated frequency |
50/60HZ |
Input |
|
Voltage range |
380/400/415V ± 20% |
Input mode |
3 phase 4 wire + ground wire / single phase 2 wire + ground wire |
Frequency range |
45Hz-55H |
Input power factor |
≥ 0.99 |
Total harmonic distortion |
<3% |
Slow start |
>60sec |
Output |
|
Voltage accuracy |
220V (Single phase) 380/400/415V (3 phase) |
Frequency accuracy |
When the frequency of utility power is 50HZ±2%, the output frequency of UPS follows the utility power frequency, and the phase difference is < 3°; when the frequency of utility power is beyond the 50Hz±0.2% or when the battery offers power, the output frequency is 50Hz±0.2%. |
Power factor |
0.8 |
Harmonic Distortion |
Linear load ≤3% , non-linear load ≤5% |
Current Crest Ratio |
3:1 |
Whole unit efficiency |
≥95% (AC power) ≥98% (Battery Powered) |
Current sharing accuracy |
≤5% |
Transfer time |
0ms |
Dynamic response transient range |
Overload 10%~100% or 100%~10%, the output voltage is ≤2% |
Load unbalance capability |
Can endure 100% unbalanced load |
DC |
|
Input rated voltage |
±384V |
Input voltage range |
345V~440V |
Panel display |
|
LCD |
Chinese/English display UPS status, input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and warning. |
Working environment |
|
Temperature |
0~40℃ |
Humidity |
0~95%, non-condensing |
Storage temperature |
-25℃~55℃ |
Altitude |
≤ sea level 1500m |
Noise(within 1m) |
< 50dB |
Physical property |
|
Size W × D× H(mm) |
600 × 800 × 2000 |
Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2 GB/17626.2~5/IEC61000-4-2~5 SAFETY:GB4943
Note: Product specifications are subject to change without further notice.
UPS Modules
Static Switches
Communication & Monitoring Module
Enter Your Message