Detail Information

Rated Input Voltage: 380/400/415VAC 3-phase 4-wire Rated Frequency: 50/60HZ
Input Parameters Input Voltage Range: ±25% Input Frequency Range: 45Hz~65Hz
Input Soft Start Function: 0-100% 5-300settable Input Power Factor: >0.98(If Harmonic Filter Is Added)
Input Harmonic Current (THDi): <4.5%(If Harmonic Filter Is Added) Bypass Voltage Range: -20%~+15%
Bypass Frequency Range: 50/60HZ±10%
High Light:

uninterruptable power supply

,

remote control ups

Product Description

Possess Date Center and Local area Networks function UPS Series 160KVA /  3Ph in / out 12p / 6p

 

Key Features:

1. On-Line Dual Conversion, fully isolating the influences of power grid pollution and power failure from utility power supply and diesel generator to load


2. Rated at 0.9 output power factor, more applicable to server computer and network center that use PFC technology in a large scale, and deliver more Active power than conventional UPS


3. Use advanced 6th generation DSP and full digital control technologies to realize higher system stability


4. Multi input harmonic suppressing technology improves the utility rate of electric Power Output isolation transformer with zero phase shift reduces the influences of Neutral to Ground voltage and load harmonic current to inverter


5. Extra strong capability to withstand output overload and short circuit, ensuring the system stability and system safety under extreme conditions


6. Advanced distributed active parallel technology can realize parallel operation of six UPS units without the need of centralized bypass cabinet


7. Extra wide input voltage and frequency range make it adapt to severe power grid environment


8. Standard input/output filter improves the system EMC performance


9.Intelligent battery management maintains battery automatically to prolong the battery life

 

10.6 inch extra large LCD that can display 12 language(Chinese.English.Russian.Spanish.French and so on


11. Layered independently-sealed ventilation channel and redundant fan, circuit boards with protective paints and a dust filter embedded make it highly efficient to dissipate heat and protect the product effectively under severe environment.


Applications:
Mainly used in large IDC rooms, bank/securities settlement center, communication network management center, semiconductor product lines and large automation production and its control system. According to the special needs of users was improved, and used in large sports venues, conference room, theater and highway and railway tunnels metal halide lamp lighting system.


 

Technical Specifications of Online UPS GP9335C 120-800KVA


Model

GP9335C  120-800KVA

Rectifier Type

6p

12p

6p

12p

6p

12p

6p

12p

6p

12p

Rated Nominal

120KVA/108KW

160KVA/144KVA

200KVA/180KW

300KVA/270KW

400KVA/36W

Rated input voltage

380/400/415VAC 3-phase 4-wire

Rated frequency

50/60HZ

Input parameters

Input voltage range

±25%

Input frequency range

45Hz~65Hz

Input soft start function

0-100%   5-300settable

Input power factor

>0.98(If harmonic filter is added)

Input harmonic current (THDi)

<4.5%(If harmonic filter is added)

Bypass

Bypass voltage range

-20%~+15%

Bypass frequency range

50/60HZ±10%

Output parameters

Inverter output voltage

380/400/415VAC 3-phase 4-wire

Voltage stability

±1%(Steady status), ±3%(Transient status)

Frequency

50/60Hz

Mains power synchronization window

±5%

Actually measured frequency accuracy (internal clock)

50/60Hz±0.01Hz

Output power factor

0.9(Output 90kW per 100kVA)

Transient response time

<5ms

Inverter overload capability

At 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s

 

Short circuit current from inverter

3ph 1.5ln for 5seconds, 1ph 2.9ln for 5seconds

Maximum Bypass capability

1000% for 100ms

 

Phase shift
characteristic

With 100% balanced load

<1°

With 100% imbalance load

<1°

 

Total harmonic
Distortion(THDv)

100% linear load

<1%

100% non-linear load

<3%

System efficiency (full load)

Up to 94% (inverter efficiency is up to 98%)

Rectifier output parameters

Charger output voltage stability

1%

DC ripple voltage

≤1%

Operating environment

Operating temperature range

0~40℃

Storage temperature

-25~70℃(Without battery)

Relative humidity

0~95% No condensation

Maximum operating height

≤Elevation 1000m, for elevation above 1000m, derate by 1% for every increase of 100m

Noise (1m)

58-68dB

Protection level

IP20

Standard

Safety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design and Test IEC62040-3

Physical parameters

Weight (kg)

980

1420

1200

1750

1350

2000

1600

2200

2100

2750

Width(mm)

900

1250

1250

1640

1250

1640

1640

2280

2280

2280

Depth (mm)

855

855

855

855

855

855

855

855

855

855

Height (mm)

1900

1900

1900

1900

1900

1900

1900

1900

1900

1900

Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2  GB/17626.2~5/IEC61000-4-2~5     SAFETY:GB4943